3-Phase Contactor Pakistan: DOL Star-Delta Wiring
3 Phase Contactor Pakistan — Wiring Star-Delta, DOL & Reversing Diagrams Guide
Updated: May 2026 · CNC Electric Pakistan
3-Phase Contactor Wiring — Pakistan Quick Answer (2026)
Three classic Pakistani 3-phase contactor wiring patterns: DOL (Direct-On-Line) — single contactor, motor starts at full voltage immediately; Star-Delta — two contactors + timer, motor starts in star (reduced voltage) then switches to delta (full voltage) at speed; Reversing — two interlocked contactors swap two phases to reverse direction. Pakistan 2026 prices: 9 A contactor Rs.850; 25 A Rs.1,650; 40 A Rs.2,800; 65 A Rs.4,500; 95 A Rs.7,200; timer relay Rs.520-850; thermal overload Rs.1,200-2,800.
Browse: CNC Contactors → · Push Buttons → · WhatsApp 0326-1111376
Pattern 1 — DOL (Direct-On-Line) Starter
The simplest 3-phase motor starter. Single contactor switches all three phases simultaneously. Motor sees full voltage immediately and accelerates to running speed.
Power circuit wiring
- 3-phase supply R + Y + B → upstream MCCB (sized to 1.25× motor FLA)
- MCCB outputs → contactor power input terminals L1, L2, L3
- Contactor power outputs T1, T2, T3 → thermal overload relay input
- Thermal overload outputs → motor U, V, W terminals
Control circuit wiring (220 V)
- 220 V control supply (Live) → STOP push button (NC) → START push button (NO) → contactor coil A1
- Contactor coil A2 → 220 V control supply (Neutral)
- Contactor auxiliary NO contact wired across the START button (the "seal-in" contact)
- Thermal overload trip contact (NC) in series with the contactor coil — opens when overload trips, drops the coil
How it operates
Press START → coil energises → main contacts close, all 3 phases reach motor → motor runs. Seal-in contact closes, keeping the coil energised after START is released. Press STOP → coil drops → contacts open → motor stops. Thermal overload on sustained current = trip → opens → coil drops → motor stops.
When to use DOL
- Motors up to 10-15 HP where starting inrush (6-8× FLA) is acceptable
- Standard pumps, fans, compressors with no special starting requirements
- Light commercial applications where simplicity matters more than start current
Pattern 2 — Star-Delta Starter
Reduces starting current by initially connecting the motor windings in STAR (each winding sees line voltage / √3 = 220 V), then switching to DELTA (each winding sees full line-to-line voltage = 380 V) once the motor is at speed. Reduces starting inrush from 6-8× FLA to 2-3× FLA.
Three contactors required
- K1 (Main / Line) — feeds the motor's start of windings (U1, V1, W1)
- K2 (Star) — shorts the ends of the windings (U2, V2, W2) together at the star point
- K3 (Delta) — connects the ends of one winding to the start of the next (creating delta configuration)
Sequence (typical 8-10 second star, then transition to delta)
- Press START: timer starts, K1 + K2 energise → motor in STAR. Motor accelerates to ~70-80% of synchronous speed.
- Timer expires: K2 drops first (delay typical 50-100 ms transition), K3 energises → motor in DELTA. Motor reaches full speed.
- Mechanical and electrical interlocks: K2 and K3 must NEVER be closed simultaneously (would short the supply). Hard mechanical interlock + auxiliary NC contacts wired in series with each other's coils.
When to use Star-Delta
- Motors 15-50 HP where DOL inrush would trip upstream breakers or cause WAPDA voltage sag
- Loads with low starting torque requirements (centrifugal pumps, fans) — high-torque loads can stall in star
- Industrial environments with reliable, repeatable operation
Required components
- 3× contactors (matched, sized to motor FLA — for 30 HP use 65 A series)
- 1× timer relay (8-12 second range, with delta-output contact)
- 1× thermal overload (set to motor delta-run FLA)
- Mechanical interlock between K2 and K3
- Standard START + STOP push buttons
Pattern 3 — Reversing (FWD/REV) Starter
Allows motor to run in either direction. Achieved by swapping any TWO of the three phases — typically R and B exchange. Two contactors with mechanical and electrical interlocks ensure both phases can never close simultaneously (which would short two phases together).
Power circuit
- K-FWD contactor: feeds motor as R, Y, B
- K-REV contactor: feeds motor as B, Y, R (swap of L1 and L3)
- Both contactors feed into the same thermal overload, then to the motor terminals
Control circuit
- STOP push button (NC) — breaks both coil circuits simultaneously
- FORWARD push button (NO) → through K-REV NC auxiliary (interlock) → K-FWD coil A1
- REVERSE push button (NO) → through K-FWD NC auxiliary (interlock) → K-REV coil A1
- Seal-in contacts on each contactor's NO auxiliary across the corresponding START button
Interlock logic
If FWD is running, K-FWD's NC auxiliary is OPEN — blocking the K-REV coil. To reverse, operator must press STOP first (drops K-FWD, closes its NC auxiliary), THEN press REVERSE. Hardware logic prevents the operator from accidentally shorting two phases together.
When to use Reversing
- Lifts and elevators (cabin goes up and down)
- Conveyor belts that need to clear jams in reverse
- CNC machinery with bidirectional tool feeds
- Pumps with reverse-flow cleaning cycles
Common Wiring Mistakes Across All Three Patterns
- Skipping the seal-in auxiliary contact. Motor only runs while START button is held — release and it stops. Add the NO seal-in contact across the START button.
- Skipping thermal overload. Contactor handles short-circuit (via upstream MCCB) but NOT sustained overload — that's the thermal relay's job. Without it, a stuck pump overheats the motor and burns the windings.
- Wrong coil voltage. Wiring a 110 V coil to 220 V supply burns it out in seconds. Always check the coil voltage stamp.
- Forgetting the interlock in reversing or star-delta. Without interlocks, two contactors can close simultaneously — short-circuiting the supply.
- Sizing the contactor on starting current instead of running. The AC3 amp rating handles starting inrush — size to motor FLA, not 6× FLA.
- No control fuse or MCB. A fault on the 220 V control circuit can damage the contactor coil and create fire risk. Use a small 2 A fuse or MCB on the control supply.
Frequently Asked Questions
How do I wire a 3-phase contactor for a motor?
Power: 3-phase supply → MCCB → contactor input (L1, L2, L3) → thermal overload → motor (U, V, W). Control: 220 V live → STOP (NC) → START (NO) → coil A1; coil A2 → neutral. Add a seal-in NO auxiliary across the START button.
What is a DOL motor starter?
Direct-On-Line — the simplest 3-phase starter. A single contactor switches all 3 phases simultaneously, applying full voltage to the motor. Suitable for motors up to 10-15 HP where the starting inrush (6-8× FLA) is acceptable.
When do I need a star-delta starter?
For motors above 15 HP where DOL starting current would trip upstream breakers or cause WAPDA voltage sag. Star-delta reduces starting inrush from 6-8× to 2-3× FLA. Best for centrifugal pumps and fans (low starting torque requirements).
How does a reversing starter prevent short circuit?
Through electrical and mechanical interlocks. Each direction contactor's NC auxiliary contact is wired in series with the OTHER direction's coil. If FWD is energised, REV cannot energise. Plus a hard mechanical interlock prevents both contactors from physically closing simultaneously.
What is the seal-in contact?
An NO auxiliary contact on the contactor wired in parallel with the START push button. Once the contactor energises, the seal-in contact closes — keeping the coil energised even after the START button is released. Without it, the motor stops the moment you release START.
What size contactor for a 20 HP 3-phase motor?
20 HP 3-phase 380 V motor draws ~30 A FLA. Use a 40 A AC3 contactor (CNC CJX2-4011, Rs.2,800). Match the thermal overload to 30 A. For star-delta starting, use three matched 40 A contactors plus a timer.
What is the price of contactors for a star-delta starter?
For a 30 HP motor (FLA 45 A, runs at delta): 3× 65 A AC3 contactors (CNC CJX2-6511 Rs.4,500 each = Rs.13,500) + timer relay (Rs.850) + thermal overload (Rs.2,800) + auxiliaries + push buttons = approximately Rs.18,500 in components.
DOL, Star-Delta, or Reversing — complete starter kits
Send motor HP / FLA / application — we’ll quote contactors + overload + push buttons + timer + isolator as a complete kit.
Browse Contactors → | Push Buttons → | WhatsApp: 0326-1111376
Related Collections & Guides
Magnetic Contactor Wiring — Pakistan-Specific Diagrams
The most common wiring questions Pakistani electricians ask about magnetic contactors:
1. Single-phase contactor + push-button START/STOP (most common home application)
L1 ━━━━━━━━━━━━━━━━━━━┳━━━━━━━━━━━━━━━━━━━━━ Motor L1
┃
┃ [STOP-NC]
┃ ┃ ┃
┃ ┃ ┃ [START-NO]
┃ ┃ ┗━━━━━┓ ┃
┃ ┃ ┃ ┃
┃ ┃ [A1] [Aux NO 13-14]
┃ ┗━━━━━━━┻━━━━━━━━━━━━━ Coil + Hold-in
┃ ┃
┃ [A2]
┃ ┃
N ━━━━━━━━━━━━━━━━━━━┻━━━━━━━━━━━━━━━━━━━━━━━━━━━━━┻━ Motor N
Key wiring rules: STOP button is normally-closed (NC) — broken wire = motor stops (fail-safe). START is normally-open (NO), held in by the contactor's own auxiliary contact (13-14). Coil terminals are A1+A2; coil voltage must match supply (230V AC most common in Pakistan).
2. 3-Phase DOL (Direct On-Line) Starter Wiring
L1 L2 L3 U V W (Motor) ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ [Contactor main: 1-2 / 3-4 / 5-6 / N-N] ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ [Overload Relay: 95-96-97-98 (trip aux)] ┃ ┃ ┃ ┃ ┃ ┃ Control circuit (drawn from L1 + N or separate 24V) ┃ ┃ ┃ ┏━━[STOP-NC]━━[START-NO]━━┓ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ [Aux 13-14]──┐ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ ┃ [A1] ┃ ┃ ┃ ┃ ┗━━━━━━━━━━━━━━━━━━━━━━━━━━┛ ┃ ┃ ┃ [A2] ┃ ┃ ┃ ┃ ┃ ┃ ┃ Overload NC 95-96 ┃ ┃ ┃ ┃ L1 (or N if 24V control)
Critical detail: the overload relay's 95-96 NC trip contact MUST be wired in series with the contactor coil. When overload trips, coil de-energises and motor stops. Without this, the overload relay does nothing useful.
3. Reversing Contactor (Forward / Reverse swap)
[Forward Contactor K1]: L1→U, L2→V, L3→W
[Reverse Contactor K2]: L1→W, L2→V, L3→U (swap L1 and L3)
Mechanical interlock between K1 and K2 — physical bar that prevents both
from closing at once. Required to avoid L1-L3 short circuit.
Electrical interlock:
K1 coil ━┳━[FWD button NO]━[K2 aux NC 21-22]━[A1 of K1]
K2 coil ━┻━[REV button NO]━[K1 aux NC 21-22]━[A1 of K2]
Both must STOP before reversing direction (typically 1-2 sec delay via timer). Direct fwd→rev without stop will burn out motor windings on most induction motors.
4. Star-Delta Starter Wiring (DOL for motors > 5HP)
3 contactors required: Main (KM), Star (KS), Delta (KD). Sequence:
- Start: KM closes + KS closes simultaneously → motor windings in star configuration (1/3 voltage per winding = 1/3 starting current)
- Transition (after 6-12 sec, timer-controlled): KS opens, KD closes → motor windings reconnected in delta (full voltage)
- Run: KM + KD stay closed; KS is open. Motor runs at full speed.
Use a dedicated star-delta timer (CNC AH3-3 with 2 outputs + transition time) — never wire star-delta logic from raw contactors and pushbuttons.
Common Pakistani Contactor Brands & CNC Equivalents
| Pakistani Brand | Model | CNC Equivalent |
|---|---|---|
| Chint | NXC-9 / 12 / 18 / 25 / 32 / 40 | CNC YC1-09 / 12 / 18 / 25 / 32 / 40 |
| Schneider | LC1D09 / D12 / D18 / D25 | CNC YC1-09 / 12 / 18 / 25 |
| ABB | AF09 / AF16 / AF26 | CNC YC1-09 / 18 / 25 |
| Siemens | 3RT2017 / 3RT2023 / 3RT2025 | CNC YC1-12 / 18 / 25 |
| Mora | LC1-D09 / D18 / D32 | CNC YC1-09 / 18 / 32 |
